Product Overview

The LM150-23BxxR2S Series is a second-generation, ultra-compact industrial standard power supply in a metal enclosure from MORNSUN, representing a comprehensive design innovation in size, performance, and reliability. It is the optimal choice for applications demanding high power density and robust performance. This series features a universal input voltage range, dual AC/DC input capability, superior cost-effectiveness, low power consumption, high efficiency, and reinforced safety isolation. The product is safe, reliable, and delivers excellent EMC performance.

Product Models: LM150-23B05R2S, LM150-23B12R2S, LM150-23B15R2S, LM150-23B24R2S, LM150-23B36R2S, LM150-23B48R2S, LM150-23B54R2S

Key Features

  • High Power Density: Compact 159mm x 97mm x 40mm metal enclosure for 150W output.
  • Universal Input Range: 80 - 305VAC / 100 - 430VDC (Dual-use AC/DC input on the same terminals).
  • High Efficiency: Up to 93.0% typical efficiency (at 230VAC).
  • Wide Operating Temperature: -40°C to +70°C (with derating up to +85°C).
  • High Isolation: 3000VAC input-output isolation (for 1 minute).
  • Low Standby Power Consumption: <0.75W (at 230VAC).
  • Low Ripple & Noise.
  • Comprehensive Protections: Short-circuit protection (Hiccup mode, self-recovery), over-current protection (110% - 150% Io, Constant current limiting, self-recovery), over-voltage protection (Clamping, self-recovery).
  • High-Altitude Operation: Suitable for applications up to 5000 meters.
  • Safety Compliance: Meets EN62477 Overvoltage Category III requirements.
  • High Reliability & Warranty: 3-year warranty.

Applications

Industrial controls, LED display screens, security systems, telecommunications, instrumentation, and other fields requiring high-reliability power.

Safety & EMC Compliance

  • Safety Standards: Certified to GB4943.1 & BS EN/EN62368-1; complies with UL/IEC62368-1, IS13252 (Part 1), BS EN/EN60335-1, BS EN/EN61558-1, EN62477-1. Safety Class I.
  • EMC Standards:
    • EMI: Conducted and Radiated Disturbance meets CISPR32/EN55032 Class B.
    • EMS: Complies with IEC/EN61000-4 series, including ESD (Contact ±4kV/Air ±8kV), Radiated Immunity (10V/m), EFT/Burst (±2kV for power, ±1kV for I/O), Surge (Line-Line ±2kV/Line-PE ±4kV) etc., Performance Criterion A.

Model Selection & Output Parameters

The product is available in standard and enhanced versions: LM150-23BxxR2S-Q (with conformal coating) and LM150-23BxxR2S-QG (with double-sided conformal coating). Various kits are available.

Detailed Model Specifications:

  • LM150-23B05R2S: Output Power 150W, Rated Output 5V/30A, Output Voltage Adjustment Range 4.75-5.5V, Typical Efficiency 88.5% (230VAC).
  • LM150-23B12R2S: Output Power 156W, Rated Output 12V/13A, Output Voltage Adjustment Range 10.8-13.2V, Typical Efficiency 91.5%.
  • LM150-23B15R2S: Output Power 157.5W, Rated Output 15V/10.5A, Output Voltage Adjustment Range 13.5-16.5V, Typical Efficiency 92.0%.
  • LM150-23B24R2S: Output Power 158.4W, Rated Output 24V/6.6A, Output Voltage Adjustment Range 21.6-26.4V, Typical Efficiency 93.0%.
  • LM150-23B36R2S: Output Power 154.8W, Rated Output 36V/4.3A, Output Voltage Adjustment Range 32.4-39.6V, Typical Efficiency 93.0%.
  • LM150-23B48R2S: Output Power 153.6W, Rated Output 48V/3.2A, Output Voltage Adjustment Range 43.2-52.8V, Typical Efficiency 93.0%.
  • LM150-23B54R2S: Output Power 151.2W, Rated Output 54V/2.8A, Output Voltage Adjustment Range 48.6-59.4V, Typical Efficiency 93.0%.

Detailed Electrical Specifications

Input Characteristics:

  • Input Voltage Range: 80-305VAC; 100-430VDC.
  • Input Frequency: 47-63 Hz.
  • Input Current (Max.): 4.0A @ 115VAC; 2.2A @ 230VAC.
  • Inrush Current (Max.): Cold start: 50A (peak) @ 115VAC, 80A (peak) @ 230VAC.
  • Leakage Current: <2.0mA @ 264VAC.
  • Efficiency: Meets DOE Level VI and COC Tier 2 standards.

Output Characteristics:

  • Output Voltage Accuracy: ±2% (over full line, load, and temperature range).
  • Line Regulation: ±0.5% (for 5V model: 90-305VAC; for others: 80-305VAC).
  • Load Regulation: ±1% (10%-100% load for 5V model); ±0.5% (20%-100% load for other models).
  • Output Ripple & Noise (Peak-to-Peak, 20MHz BW):
    • 5V model: 100mV max.
    • 12V, 15V models: 120mV max.
    • 24V, 36V, 48V, 54V models: 150mV max.
  • Temperature Coefficient: ±0.03%/°C.
  • Minimum Load: 10% (for stable startup and operation of 5V model).
  • Standby Power: <0.75W @ 230VAC.
  • Hold-up Time: Typ. 20ms @ 115VAC; Typ. 60ms @ 230VAC.

General Characteristics:

  • Isolation Resistance: ≥100MΩ (tested at 500VDC).
  • Operating & Storage Temperature: -40°C to +85°C.
  • Operating & Storage Humidity: 20% to 90% RH (non-condensing).
  • Switching Frequency: Typ. 100kHz.
  • Output Power Derating:
    • Temperature Derating: Required above +70°C up to +85°C.
    • Input Voltage Derating: Required for input voltages below 100VAC.

Physical & Mechanical Characteristics

  • Enclosure Material: Metal (AL5052, SGCC).
  • Dimensions: 159.00 x 97.00 x 40.00 mm (L x W x H).
  • Weight: Typ. 580g.
  • Cooling Method: Natural air convection or forced air cooling (with external fan).
  • Output Voltage Adjustment: Adjustable via the onboard ADJ potentiometer (clockwise to increase).
  • Installation: For end-use applications, the enclosure must be reliably connected to protective earth (PE).

Important Notes

  1. All specifications are measured at 25°C ambient temperature, 230VAC input, and rated output load, unless otherwise stated.
  2. Derating is required for high-altitude applications: above 2000m, the operating temperature must be derated.
  3. A minimum load (e.g., 10% for 5V model) is required for stable startup and operation.
  4. Forced air cooling is recommended for full-load operation, especially at high ambient temperatures. Refer to the derating curves.
  5. The ripple and noise measurement method uses a parallel 10µF ceramic capacitor and a 47µF electrolytic capacitor at the output.
  6. The power supply is a component. Final system EMC, safety, and thermal performance must be validated in the end equipment.
  7. Customized versions (e.g., modified output voltage) are available. Please contact us for specific requirements.
  8. The "P" pin (case ground) must be connected to the system's protective earth (PE).